David J. Wyatt, CDT Senior Member Username: david_j_wyatt_cdt
Post Number: 57 Registered: 03-2011
| Posted on Thursday, January 23, 2014 - 11:17 am: | |
I am averse to specifying sound batts in Division 07 - especially if I don't have any other insulation. I am inclined to specify them in 09 8116 - Acoustic Blanket Insulation. Am I thinking right? |
Dave Metzger Senior Member Username: davemetzger
Post Number: 490 Registered: 07-2001
| Posted on Thursday, January 23, 2014 - 12:00 pm: | |
If their only location is in metal stud-framed gypsum board partitions, I specify acoustic batt/blanket insulation in 092900 Gypsum Board. I used 098116 only if the insulation is used in wood stud-framed partitions. I have used 098100 Acoustic Insulation mostly for theater or broadcasting projects, where there has been multiple types of acoustic insulation. |
Margaret G. Chewning FCSI CCS Senior Member Username: presbspec
Post Number: 242 Registered: 01-2003
| Posted on Thursday, January 23, 2014 - 12:01 pm: | |
Often I'll include the sound batts in 09 21 16 - Gypsum Wall Assemblies. |
Jeffrey Wilson CSI CCS Senior Member Username: wilsonconsulting
Post Number: 122 Registered: 03-2006
| Posted on Thursday, January 23, 2014 - 12:17 pm: | |
I typically use 09 8116 because sound batts are frequently used in multiple applications. This avoids having redundant provisions in several sections (shaftwall, gyp board, etc). |
David J. Wyatt, CDT Senior Member Username: david_j_wyatt_cdt
Post Number: 58 Registered: 03-2011
| Posted on Thursday, January 23, 2014 - 12:35 pm: | |
Thanks, everyone, for your perspective on this. |