It's RFI week for me!!!
If a rated door assembly is tested by WH (instead of UL), would WH still neet to test (and show compliance with) UL 10c (or is that test only performed by UL)?
ken hercenberg
Senior Member
Username: khercenberg

Post Number: 717
Registered: 12-2006


Posted on Thursday, February 27, 2014 - 05:19 pm:   Edit PostDelete PostPrint Post

As far as I know, Interetek (WH) tests to UL 10(c) and many other standards.

Check out their directory at https://whdirectory.intertek.com/Pages/DLP_Search.aspx
Mark Gilligan SE,
Senior Member
Username: mark_gilligan

Post Number: 645
Registered: 10-2007
Posted on Friday, February 28, 2014 - 09:08 pm:   Edit PostDelete PostPrint Post

WH needs to test to the standard listed in the code. If the code required UL to perform the test we would have a monopoly. If the Owner wishes to only allow tests per UL and states so in the specification then there is no problem.