Has anyone here specified an open joint rainscreen system as a contractor design build? When I say rainscreen system I mean to include: fasteners, insulation, z-girts, weather barrier, panels and mounting system. |
(Unregistered Guest) Unregistered guest
| Posted on Thursday, April 15, 2010 - 06:08 pm: | |
Easy. Require that system pass AAMA 508 and you will be fine. |
Anne Whitacre, FCSI CCS Senior Member Username: awhitacre
Post Number: 944 Registered: 07-2002
| Posted on Monday, April 19, 2010 - 05:10 pm: | |
yes, but you have to give all the design criteria you care about, and all the testing criteria they are expected to meet. In addition, you need to draw the scope of work very carefully at the junction between the wall system and the supports, the sealants, drains, and other accessory items. but yes, I've done a lot of them. |
|